XM31-918-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-918-HP
Firmware V1.04.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 124.12 V
Current 5.38 A
Power 526 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 0 Wh
Output
Voltage 87.01 V
Power 400 W
Apparent Power 428.95 VA
Frequency 60.06 Hz
Percent Load 27.30 %
Output Setting 90 V
Output Regulation Coarse override
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Current 4.93 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 142
Time Since Last Standby Event 147d 13h:22m
Time in Last Standby Event 0d 0h:01m
Total Time in Standby 1,683 min
Standby Events Since Reset 81
Time in Standby Since Reset 1,048 min
Time Since Reset 1,161 day(s)
Total Run Time 1,161 day(s)
Transformer Run Time 1,161 day(s)
Total Downtime 0d 0h:00m
Oil Cap Lifespan Consumed 0.0 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 15 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2017-2022 EnerSys. All Rights Reserved.
www.alpha.com   |   www.enersys.com